Liebert 128158P2S 1/2X5/8X1/4Odf Thermal Expansion Valve(Txv) Valve

Special Price $226.62 Regular Price $251.55
In stock
SKU
128158P2S
The Liebert 128158P2S Thermal Expansion Valve 1/2" X 5/8" X 1/4" ODF is used to control refrigerant flow in HVAC systems to achieve accurate cooling & optimum operation of the parts. It has a major role in regulating the quantity of refrigerant to the evaporator depending on thermal load with a temperature-sensitive sensing mechanism. The valve is mounted on the line with open-die-faced connections with the sizes to ensure a fit. It is appropriate in air conditioning, where the distribution maintains a steady temperature and operational efficiency.
Manufacturer:
https://www.partshnc.com/media/catalog/product/1/2/128158p2s.jpg

PRODUCT OVERVIEW:
The thermal expansion valve controls refrigerant delivery into the evaporator to support proper heat absorption and stable refrigeration operation. The Liebert 128158P2S is an OEM replacement valve designed for compatible Liebert cooling equipment. Its thermostatic metering mechanism regulates refrigerant supply in response to changing evaporator conditions, helping maintain appropriate system operation.

REFRIGERANT METERING:
The valve regulates refrigerant flow through an internal metering orifice. Its thermostatic sensing mechanism responds to temperature changes at the evaporator outlet and adjusts the valve opening to control refrigerant supply. This modulation helps maintain appropriate evaporator feeding and superheat as the cooling load changes.

PRESSURE CONTROL:
The valve creates a pressure reduction between the high-pressure liquid line and the lower-pressure evaporator circuit. As refrigerant passes through the restricted metering opening, its pressure decreases before entering the evaporator. This controlled expansion prepares the refrigerant for heat absorption within the evaporator coil.

REPLACEMENT GUIDELINES:
Replace the thermal expansion valve when internal blockage, mechanical wear, or loss of thermostatic response prevents proper refrigerant metering. Before replacement, inspect the sensing assembly and refrigerant circuit for contamination, damage, or restrictions that could affect the new valve. A qualified HVAC technician should verify the replacement part against the equipment documentation and check system operation after servicing.

COMMON FAILURE SYMPTOMS:

  • Reduced cooling performance due to improper refrigerant flow.
  • Unstable evaporator superheat readings.
  • Abnormally low suction pressure during operation.
  • Frost or ice accumulation on the evaporator coil.
  • Inconsistent refrigerant feeding under changing cooling loads.

EQUIPMENT COMPATIBILITY:
The Liebert 128158P2S thermal expansion valve is intended for compatible Liebert HVAC and precision cooling equipment. Verify the part number and all three connection dimensions against the equipment manufacturer's parts documentation and unit model before ordering.

TECHNICAL SPECIFICATIONS:
Product Identification:
Brand: Liebert
Part Number/SKU: 128158P2S
Component Type: Thermal Expansion Valve
Physical Specifications:
Connection Sizes: 1/2 Inch × 5/8 Inch × 1/4 Inch ODF

Write Your Own Review
You're reviewing:Liebert 128158P2S 1/2X5/8X1/4Odf Thermal Expansion Valve(Txv) Valve
Your Rating
Customer Questions
What maintenance is required for the Liebert 128158P2S Thermal Expansion Valve?

Inspect valve for refrigerant leaks and ensure sensing bulb is securely attached and insulated. Clean external connections and check for clogging or debris affecting flow. Regular maintenance ensures stable superheat control and prevents system inefficiency or compressor strain.

What are common issues with the Liebert 128158P2S Thermal Expansion Valve?

  • Stuck or sticking valve causing improper refrigerant flow.
  • Erratic superheat control.
  • Clogging in orifice or debris blockage.
  • Sensor bulb failure or poor response.
  • Refrigerant underfeeding or overfeeding.
  • Fluctuating pressure control.

What is the primary function of the Liebert 128158P2S valve?

It regulates liquid refrigerant flow into the evaporator, helping maintain controlled refrigerant feeding during cooling operation.

How does the valve respond to changes in cooling demand?

Its thermostatic sensing mechanism adjusts the internal metering opening in response to changing evaporator conditions.

What happens when the valve becomes internally restricted?

Restricted refrigerant flow can reduce evaporator feeding, resulting in poor cooling performance and abnormal superheat conditions.

Why is superheat important when evaluating valve performance?

Superheat measurements help determine whether the evaporator is receiving an appropriate amount of refrigerant under the current operating conditions.

Can incorrect valve selection affect refrigeration system operation?

Yes. An incorrectly selected valve may provide unsuitable refrigerant flow, affecting evaporator performance and overall system operation.

Installation Steps

Step 1: Turn off power and recover refrigerant safely using better equipment properly.

Step 2: Remove access panels and carefully disconnect old valve and sensing bulb.

Step 3: Braze new valve into refrigerant line with nitrogen purge during brazing.

Step 4: Mount sensing bulb tightly on suction line and insulate properly.

Step 5: Evacuate system, leak test, and recharge to spec properly.

Step 6: Restore power and check superheat and cooling performance properly.